MENU

Indoor load break switches QDS

Indoor load break switches QDS

Technical information

Rated voltage: 1 – 25 kV
Rated current: 100 – 2000 A
Rated shorttime current 1s (3s): 16 – 40 kA
Rated dynamic current: 40 – 100 kA
Rated making short circuit current: 12,5 kA
Rated frequency: 50 Hz
Mechanical endurance: 2000 C-O
Minimum lifetime (years): 40
Drive type: Hand drive, Hand drive via gearbox, motor drive
Motor type: 12V DC, 24V DC, 48V DC, 60V DC, 110V DC, 220V DC, 230V AC, 400V AC
Signaling positions:Limit switches per position, placed direct on main device shaft, Auxiliary cam-switch (high switch capacity)
Insulators type: Epoxy resin, porcelain (upon request)

QR Link

http://manual.ivep.cz/qds